EHP air conditioner | Frame part number | |
---|---|---|
Outdoor unit | Multi for building | BM |
Other than building multi | ABM | |
AY | ||
Indoor unit | - | ABMR |
ARY |
Anti-vibration performance | Natural frequency about 6Hz (coil spring specification) |
---|---|
Seismic performance | Design seismic intensity horizontal 2G, vertical 1G (Anti-vibration compatible product available) |
Anti-corrosion measures | HDZT 56 equivalent |
・Excitation sources are fans and compressors, but the actual problem is the excitation force of the compressor.
・This excitation force has a frequency component of about 10 to 150 Hz and is not particularly large, but noise interference may occur depending on the conditions of the installation floor.
・A coil spring is built into the weather-resistant resin casing.
Equipped with a mechanism to prevent natural vibration (surging) of the coil spring itself as standard equipment.
・Anti-vibration products are also available to minimize shaking during earthquakes and strong winds.
・Safe design corresponding to design seismic intensity horizontal 2.0, vertical 1.0.
All rights reserved, © Copyright Kurashiki Kako Co., Ltd.
Feel free to contact us for a quote or inquiry