Product information

Frame

Frame for EHP air conditioner BM/ABM/ABMR/AY/ARY

Click here for inquiries about this product

Standard specifications

Part number series

EHP air conditionerFrame part number
Outdoor unitMulti for buildingBM
Other than building multiABM
AY
Indoor unit-ABMR
ARY

Standard performance

Anti-vibration performanceNatural frequency about 6Hz
(coil spring specification)
Seismic performanceDesign seismic intensity horizontal 2G, vertical 1G
(Anti-vibration compatible product available)
Anti-corrosion measuresHDZT 56 equivalent

Features

Equipment features (EHP air conditioner)

・Excitation sources are fans and compressors, but the actual problem is the excitation force of the compressor.
・This excitation force has a frequency component of about 10 to 150 Hz and is not particularly large, but noise interference may occur depending on the conditions of the installation floor.

Frame features

・A coil spring is built into the weather-resistant resin casing.
Equipped with a mechanism to prevent natural vibration (surging) of the coil spring itself as standard equipment.
・Anti-vibration products are also available to minimize shaking during earthquakes and strong winds.
・Safe design corresponding to design seismic intensity horizontal 2.0, vertical 1.0.