Chiller | Frame part number |
---|---|
Outdoor unit | CY |
Indoor unit | CRY |
Anti-vibration performance | Natural frequency about 4Hz (coil spring specification) |
---|---|
Seismic performance | Design seismic intensity horizontal 2G, vertical 1G (Anti-vibration compatible product available) |
Anti-corrosion measures | HDZT 56 equivalent |
・The sources of vibration are fans and compressors, and compressors with higher output than air conditioners are installed.
Therefore, the excitation force is very large, and the excitation frequency has a strong component up to around 250Hz.
・Because the vibration force is large and it is installed on the top floor, it is necessary to take sufficient anti-vibration measures.
・A coil spring is built into the weather-resistant resin casing.
Equipped as standard with a mechanism to prevent the natural vibration (surging) of the coil spring itself.
・Anti-vibration products are also available to minimize shaking during earthquakes and strong winds.
・Safe design with design seismic intensity of 2.0 horizontal and 1.0 vertical.
All rights reserved, © Copyright Kurashiki Kako Co., Ltd.
Feel free to contact us for a quote or inquiry