Product information

Frame

Frame GBM for GHP air conditioner

Click here for inquiries about this product

Prevents large low-frequency vibrations during startup and shutdown

Click here for drawings and selection charts

Standard specifications

Part number series

GHP air conditionerFrame part number
Outdoor unitGBM

Standard performance

Anti-vibration performanceNatural frequency about 4Hz
(coil spring specification)
Seismic performanceDesign seismic intensity horizontal 2G, vertical 1G
(standard equipment with anti-sway)
Anti-corrosion measuresEquivalent to HDZ 40

Features

Equipment features (GHP air conditioner)

・It has a large excitation force of low frequency by gas engine compressor.
・The gas pipes need to be taken into consideration, as large vibrations occur when starting and stopping.

Frame features

・Recommended by major gas companies and GHP manufacturers.
・Confirmed sufficient anti-vibration performance by conducting actual machine tests at each GHP manufacturer.
・Equipped with anti-vibration stoppers as standard to prevent damage to gas pipes due to shaking during start/stop.
・Since the position of the isolator is set in advance, horizontal leveling is almost unnecessary.
・Safe design with design seismic intensity of 2.0 horizontal and 1.0 vertical.

CONTACT

Feel free to contact us for a quote or inquiry

Feel free to contact us for a quote or inquiry