Product information

Anti-vibration material for suspension

Anti-vibration rubber RF

Click here for inquiries about this product

Performance/Features

・Can handle a wide range of loads from light loads to heavy loads.
・Since the anti-vibration rubber and the hanger are integrated, installation work is easy.
・Double nuts can be installed.

Example of installation

Specifications/Standards

RF-S (single)
RF-D (Double)
Product numberStandard dimensions (mm)Applicable boltSpring constant N/mm
{kgf/cm}
Allowable load
N{kgf}
A.B.L.D.F.D1d1H.d2t1_M.W.
RF-22S22327011222102410183/859 { 60 }230 { 23 }
RF-22D9729 { 30 }
RF-30S304465112.3301220141.6103/8140 { 140 }430 { 44 }
RF-30D9069 { 70 }
RF-40S405575152.3401424142121/2240 { 240 }860 { 88 }
RF-40D1082.6120 { 120 }
RF-50S506680153.2501422163.2121/2510 { 520 }1100 { 110 }
RF-50D107250 { 260 }
RF-60S607685153.2601427163.2121/2650 { 660 }2600 { 270 }
RF-60D117320 { 330 }
RF-80S80100120183.2801639184.512
or
16
1/2
or
5/8
810 { 830 }4800 { 490 }
RF-80D165407 { 415 }
RF-100S100130140204.51002043224.516
or
20
5/8
or
3/4
1180 { 1200 }7700 { 790 }
RF-100D170590 { 600 }
RF-100HS100130140204.51002045224.516
or
20
5/8
or
3/4
1670 { 1700 }11500 { 1170 }
RF-100HD190830 { 850 }
RF-120S120150160226120224822616
or
20
5/8
or
3/4
3500 { 3570 }25000 { 2550 }
RF-120D2201750 { 1780 }

*RF-100HS, 100HD, 120S, and 120D are not integrated with the hanger and anti-vibration rubber.

Usage range

Ministry of Land, Infrastructure, Transport and Tourism specifications: full water + heat insulation (outer galvanized steel plate)
Institute of Architects/SHASE010 specification: Plumbing + water. If heat insulating material or other mass is added, add that amount when selecting.

Main use

・Air conditioning equipment
・Package type air conditioner
・Fan coil unit
・Ventilator
・Pump
・Blower
・Duct
・Suspension support for other devices

CONTACT

Feel free to contact us for a quote or inquiry

Feel free to contact us for a quote or inquiry

Return to top of page