Click here for drawings, CAD, and construction instructions
* Building side and ground side fixed mounts are sold separately.
Workability | Working space | Cost |
---|---|---|
◎ | 〇 | △ |
・A mechanical type is adopted to absorb displacement in all directions.
・It boasts overwhelming durability compared to general SUS flexible systems.
・Because the operating space is small, there is no need to worry about the installation location.
・Can be used for high temperature systems that rubber flexible cables cannot handle.
・High heat resistance due to special surface treatment and high temperature sealing material.
・Smooth drainage is possible without stagnation in the valleys of the tube, which is unavoidable with SUS flexible cables.
・Operating temperature: oil system 60°C or less, high temperature drainage system 90°C or less
・Working pressure: oil system 1.0Mpa, high temperature drainage system atmospheric pressure
Dangerous Goods Safety Technology Association Individually rated product
Piping Nominal | For 1.0Mpa (JIS10KF connection) | |||
---|---|---|---|---|
Seismic isolation amount | ||||
500mm | 600mm | 700mm | 800mm | |
face-to-face dimension | face-to-face dimension | face-to-face dimension | face-to-face dimension | |
25A | 1820 | 2120 | 2420 | 2720 |
32A | 1850 | 2150 | 2450 | 2750 |
40A | 1860 | 2160 | 2460 | 2760 |
50A | 1930 | 2230 | 2530 | 2830 |
65A | 2000 | 2300 | 2600 | 2900 |
80A | 2220 | 2520 | 2820 | 3120 |
100A | 2290 | 2590 | 2890 | 3190 |
125A | 2300 | 2600 | 2900 | 3200 |
150A | 2370 | 2670 | 2970 | 3270 |
・Axial thrust is generated by the pressure inside the pipe, so firmly fix the front and rear of the joint.
・Because the volume inside the pipe fluctuates during seismic operation, use it in an open piping line or in a piping system that allows the volume inside the pipe to escape.
・For convenience of transportation, the product will be delivered in a contracted state.
Piping Nominal | Seismic isolation amount | |||
---|---|---|---|---|
500mm | 600mm | 700mm | 800mm | |
face-to-face dimension | face-to-face dimension | face-to-face dimension | face-to-face dimension | |
25A | 1820 | 2120 | 2420 | 2720 |
32A | 1850 | 2150 | 2450 | 2750 |
40A | 1860 | 2160 | 2460 | 2760 |
50A | 1930 | 2230 | 2530 | 2830 |
65A | 2000 | 2300 | 2600 | 2900 |
80A | 2220 | 2520 | 2820 | 3120 |
100A | 2290 | 2590 | 2890 | 3190 |
125A | 2300 | 2600 | 2900 | 3200 |
150A | 2370 | 2670 | 2970 | 3270 |
All rights reserved, © Copyright Kurashiki Kako Co., Ltd.
Feel free to contact us for a quote or inquiry