Comes with an earthquake-resistant stopper that allows the structure to avoid the provisions of the specific ceiling (Article 39, Paragraph 3 of the Building Standards Law Construction Order).
Part number | Bolt size (mm) l | Spring constant N/mm {kgf/cm} | Allowable load N {kgf} | During stopper action Allowable load in shear direction N {kgf} | Stiffness ratio Kx/Kz | Static-dynamic ratio | Paint marking | ||
---|---|---|---|---|---|---|---|---|---|
Compression direction (Z direction) | Shear direction (X direction) | Compression direction (Z direction) | Shear direction (X direction) | ||||||
SHB-65A(-L)-TS | 40 (120) | 350 { 360 } | 220 { 225 } | 1780 { 180 } | 1180 { 120 } | 20440 { 2090 } | 0.6 | 1.2 | yellow |
SHB-65B(-L)-TS | 40 (120) | 470 { 480 } | 300 { 310 } | 2380 { 240 } | 1670 { 170 } | 0.6 | 1.25 | red | |
SHB-65C(-L)-TS | 40 (120) | 610 { 620 } | 380 { 390 } | 3010 { 310 } | 2060 { 210 } | 0.6 | 1.35 | green | |
SHB-90A(-L)-TS | 39 (119) | 780 { 800 } | 320 { 330 } | 3920 { 400 } | 1760 { 180 } | 0.4 | 1.2 | orange | |
SHB-90B(-L)-TS | 39 (119) | 1000 { 1020 } | 410 { 420 } | 5000 { 510 } | 2350 { 240 } | 0.4 | 1.25 | blue | |
SHB-90C(-L)-TS | 39 (119) | 1330 { 1360 } | 540 { 550 } | 6660 { 680 } | 3040 { 310 } | 0.4 | 1.35 | pink | |
SHB-90D(-L)-TS | 39 (119) | 1550 { 1600 } | 630 { 640 } | 7740 { 790 } | 3530 { 360 } | 0.4 | 1.4 | White | |
SHB-90E(-L)-TS | 39 (119) | 1870 { 1900 } | 760 { 780 } | 9290 { 950 } | 4280 { 440 } | 0.4 | 1.5 | golden color |
*Rubber material is natural rubber compound.
*Earthquake-resistant bracket x 1, steel pipe x 2, M12 U-nut x 3, and M12 washer x 3 are included.
*For products with -L in the product number, the length is within the bolt dimensions ().